Installation
What does 1.5 or 2.5 mm² mean?
The cross-sectional area of one conductor in square millimetres. It sets how much current the cable may carry, and therefore which breaker goes in front of it.
The number printed on the cable, 1.5, 2.5 or 4, is the area of one conductor, not its diameter. Everything else follows from it.
The usual sizes in a flat
1.5 mm² carries lighting circuits, with a 10 A breaker in front of it.
2.5 mm² carries socket circuits, with 16 A.
4 mm² and above goes to a water heater, a cooker or an air conditioner, with 20 A or 25 A depending on the load.
These are indicative. The real figure depends on how the cable is installed, how long the run is and how warm it gets: a cable inside conduit in an insulated wall behaves quite differently from the same cable in open air.
Why the breaker follows the cable
This is the part people get backwards. The breaker is chosen for the cable, not for the appliance.
The cable is buried in a wall and cannot be inspected. If it carries more than it was sized for, it heats along its whole length, the insulation ages, and eventually it fails somewhere nobody can see. The breaker exists to stop that.
So fitting a larger breaker because one keeps tripping does not solve anything. It removes the only thing standing between an undersized cable and a short circuit.
Aluminium
In flats built before the eighties the wiring is often aluminium rather than copper. Aluminium carries less current for the same cross-section, so a 2.5 mm² aluminium cable is not the equal of a 2.5 mm² copper one.
It also creeps under pressure, so a joint tightened today loosens over the years and then heats up. Aluminium and copper are never joined directly but through a connector rated for it, and getting that wrong is the most common cause of an outlet that gets hot.
Long runs
Voltage drops over distance. For a supply at the bottom of a garden or the end of a long corridor a larger cross-section is sometimes chosen than the current alone would require, not because of heating but so the voltage at the far end is still usable.
All of it is set out on the drawing before anything is chased into a wall, which is part of a new installation.
See also
Circuit breaker
The cable in the wall, not the appliance. It cuts the circuit when more current flows through it than the cable can carry without overheating.
Consumer unit
The enclosure where the supply from the meter is split into circuits and where all the protection sits: main switch, RCD and breakers, in that order from left to right.
Short circuit
Live and neutral touching directly, with no appliance between them. Current jumps to hundreds of amps and the cable overheats instantly, so protection must disconnect at once.
Mentioned in
More in: Installation
Now you know what it is. Need somebody to do it?
Send photos or call — you get an estimate before anyone travels.